The demand for energy is increasing around the world due to population growth and industrialisation. Fossil fuels such as oil and natural gas are considered as primary sources of energy. In 2035 more than 80% of the energy consumption of the United States will be produced by fossil fuels [1]. Producing energy by traditional methods leads to more gas emissions and accelerated global warming. Alternative renewable sources of energy such as solar energy, wind energy and geothermal energy are required [2].
In response to the need for alternative energy sources, solar cooling technologies have become an important factor especially in hot countries due to the huge amount of solar radiation and the need for cooling. Solar cooling systems are environmentally friendly compared to conventional cooling systems and an important technology to reduce gas emissions [3]. Pazheri et al. [4] estimated that a 20 MW solar plant, which would need an area of 1.25 km2, can generate 200 to 300 GWh/year and could save 500,000 barrels of oil per year.
The potential for solar energy and the opportunity to utilize it for cooling purposes depend on the location in the world. Theoretically, 0.6% of the area of Europe would need to be covered by solar Photovoltaic (PV) panels to satisfy total Europe’s electricity consumption [5]. Europe, North America, most of Latin American and western Asia have 100–200 W/m2 average annual rate of solar radiation while in the Middle East, the value reaches up to 250 W/m2 [4]. In Europe, the residential sector accounts for about 40% of energy consumption and heating purposes represents about 68% of this sector [6], [7]. In contrast, cooling systems have been the main energy consumer in the residential sectors in hot climatic conditions. In Saudi Arabia, 72% of residential electricity is consumed by cooling equipment [8].
In the last few years, there has been a growing interest to reduce the initial cost and improve the efficiencies of solar collectors and this leads to reduce overall investment of the solar cooling system. Photovoltaic thermal collectors have been used for several solar cooling projects in order to produce both electricity and thermal energy and this also can improve electrical efficiency by 23.8% more than the conventional PV panel [9], [10]. Figure 1 shows schematic diagram of solar heating and cooling absorption system which consist of absorption chiller, storage tank, cooling space and controllers.
Schematic diagram of solar heating and cooling absorption system [10]

There has been large-scale research that studied Photovoltaic Thermal (PVT) and solar cooling systems separately. However, using PVT to power cooling systems has been rarely examined in literature. For Concentrated Photovoltaic Thermal (CPVT) and
PVT, the average area to produce cooling in the studied literature for solar absorption chillers was 2.72 m2/kWc and 3.1 m2/kWc, respectively [11].
The aim of this study is to investigate the effect of PVT outlet water and solar cell temperature on both electrical and thermal efficiency for different range of inlet water temperature in order to reach the highest overall efficiency for the solar cooling system. The study describes the design and analysis of a PVT system in Saudi Arabia climatic condition. The performance of the system is based on several factors that includes PVT materials, design, ambient temperature, inlet and outlet fluid temperature and PV cell temperature. A mathematical model was developed for a PVT system and the results validated with experimental data from [12].
Mittelman et al. [13] studied the performance and the economic viability of the use of CPVT collectors for cooling and power generation. The mass and energy balance were applied for each component in the chiller for varying generation temperature from 65 °C to 120 °C. The finding in the study indicated that electrical efficiency has significant effect of coolant outlet temperature and decreased from 23% to 20% with the increase in coolant outlet temperature from 50 °C to 150 °C while the thermal efficiency was about 60% in the same range of the coolant temperature. The authors also reported that the PV cell temperature was 10–30 °C higher than the outlet coolant temperature. In this system, the thermal energy was considered to be used directly to the absorption chiller without using storage tank which is expected to increase the overall efficiency of the system and decrease the backup heater capacity.
Vokas et al. [14] investigated the use of hybrid PVT collectors instead of Flat Plate Collector (FPC) along with absorption chiller in order to meet the cooling and heating domestic load throughout the year. The performance of the collectors was analysed for different geographical region using the approximation method F-chart. The study highlighted that electrical efficiency of the PVT has improved due to the reduction of its operation temperature and the performance was highly affected by the climate conditions. The study also revealed that FPC can cover 54.26% of the heating load and 31.87% of the cooling load while these percentages decreased by 11.9% and 21.4 in the case of PVT for heating and cooling respectively. Electrical performance for PVT and parameters for FPC weren’t reported, the results weren’t validated and further justification is needed to explain the decrease in thermal efficiency of PVT.
Calise et al. [15] investigated the performance of solar cooling and heating system based on energy saving and economic analysis by considering a specified case study of a university building in Italy. The PVT collectors of 1,000 m2 were simulated in TRNSYS to produce both electrical and heat energy to supply a 325 kWc single lithium bromide absorption chiller that operates at 80 °C, the other components were storage tank, auxiliary heater and cooling tower. The findings of this study indicated that PVT performance is significantly affected by ambient and operation temperature. The authors also found that the PVT system can produce 18% electrical efficiency at an outlet fluid temperature in the range of 60 °C to 80 °C. They also reported that the type of the cover of PVT systems is an important factor that affects the PVT performance and further research is required. They highlighted that the tube and sheet c–Si PVT systems show a good ratio of energy production for cooling and heating, but in the study, there was surplus electricity which was sold to the grid or supplied to the building for other purposes.
Calise et al. [16] investigated a dynamic simulation system for cooling, heating and other building demand for electricity in order to find the optimal capacity of a solar collectors field. The study considered a case study in Italy that included 325 kW double stage absorption chiller (LiBr–H2O) and CPVT collector area of 996 m2 and TRNSYS has been used to simulate the project throughout the year. The findings in this work highlighted that the average thermal and electrical efficiency throughout the year were 32% and 13.3% respectively. The primary energy saving and simple payback period were 84.4% and 15.2 year respectively. Furthermore, the study highlighted the need for a public fund for the CPVT cooling systems in order to become a competitor compared to conventional systems. They reported that no prototype for this system had been tested. Further research is needed to define the optimal value of the capacity and area for solar collectors.
Alobaid et al. [11] published a review paper that focused and discussed the combination of PVT collectors with absorption chiller. The authors highlighted that most of studies in PVT carried out mostly in low temperature climate and focused on heating application where the inlet temperature of PVT is close to the ambient temperature and the outlet fluid temperature less than 60 °C. Thermal collectors efficiencies were in the range of 0.06–0.64 and sufficient efficiency for the PVT could be achieved in the range of outlet temperature of 60–80 °C. Generally, the performance of the solar collector was highly affected by ambient temperature, inlet temperature, solar radiation and the configuration of the collectors.
PVT water collectors were classified based on heat exchanging method and water flow pattern into sheet and tube, channel free flow and two absorber collector [17]. The maximum thermal and electrical efficiency of sheet and tube PVT for the study were 70% and 15% respectively. The main absorber materials that are usually used as a main component in PVT and the main features that affect efficiency which included thickness, density, thermal conductivity and heat capacity are reported in Table 1.
Main features of absorber materials [17]
Absorber material |
Thickness [mm] |
Density [kg/m3] |
Thermal conductivity [W/mK] |
Heat capacity [J/kgK] |
---|---|---|---|---|
Copper |
~0.3 |
8,920 |
380 |
350 |
Aluminum |
~ 1 |
2,700 |
160 |
900 |
Steel |
~2 |
7,860 |
50 |
450 |
Polymer |
~2–3 |
900–1,500 |
0.2–0.8 |
1,200–1,800 |
Cristofari et al. [18] developed a PVT system using a finite difference method to study thermal and electrical efficiency. The authors reported that yearly average thermal and electrical efficiency was 55% and 12.7% respectively. The authors also reported that the use of copolymer in the PVT could reduce the cost and weight of the module.
Dubeyand Tay [19] developed a 10 kWp PVT array made of 52 panels. Theoretically, the performance of the system was calculated by solving energy equation with several assumptions such as: the heat capacity for the materials in the system was neglected compared to the heat capacity of the water and, one dimensional heat transfer was assumed, steady state, and no temperature stratification in the storage tank. The authors calculated the optimum flowrate for the PVT system to be 0.039 kg/sm2 and the average thermal and electric efficiency were 34% and 12% respectively.
Yazdanifard et al. [20] developed a mathematical model to investigate the effect of solar radiation, geometry and Reynolds number on the performance of flat plat PVT system. In this study, glazed PVT system provides higher efficiency compared to unglazed system. The authors reported that the length of the collector affected the total PVT efficiency.
The current developments in the field of PVT collectors for cooling purposes have been reported in this section. Efficiency for the PVT was achieved in the range of outlet temperature of 60 °C to 80 °C. Despite the fact that there has been an improvement of the electrical efficiency due to reduced the PV temperature by the coolant in the PVT system, there is an opportunity to utilize the outlet water from PVT to further enhance the solar cooling system. Electrical efficiency and thermal efficiency for the PVT are largely affected by ambient temperature and global solar radiation. The performance and outlet fluid temperature for PVT in different climate conditions and inlet temperature, requires further information.
The parameters of the PVT and the weather data were mainly taken from the experiment conducted by Bahaidara et al. [21] in Saudi weather (Dhahran). There were missing information in the experiment about some characteristics of the PVT so some parameters which included UL, UT and UtT were assumed based on Duebey [19] theoretical model. The inlet temperature in the experiment was taken from insulated tank and not given in the article. In this study the inlet temperature was assumed to be less than ambient temperature and the fluid temperature Tf was assumed to be (Ti + To)/2. The PV cell temperature was predicted during the day by the mathematical model and validated with the experiment results.
In order to solve energy equations and calculate the performance of the PVT system, the following assumptions were applied [19], [22]:
Heat capacity for the materials in the system was neglected compared to the heat capacity of the water;
Steady state, one dimensional heat transfer method was applied;
Properties were independent of temperature.
Energy balance equation was applied on the PVT collectors which consist of PV cell, plate, channel and fluid. Applying energy balance on any layer of the PVT leads to the eq. (1) which represent the change in internal energy for the PVT collectoras
Applying eq. (1) on the PV layer leads to eq. (2):
Thermal efficiency is the ratio of the collected energy to the energy that reaches the solar collector area. Thermal efficiency is calculated by the following expression [19], [12], [24]:
The useful energy is calculated by the following expression [12], [19], [22], [25]:
In order to calculate useful energy from eq. (4), the plate temperature needs to be measured or calculated. For this reason, heat removal factor (FR) and inlet fluid temperature (Ti) were added to eq. (4) to be written as:
or:
Collector heat removal factor (FR) is the ratio of actual useful energy gain of a collector to the useful gain if the collector surface is assumed at the inlet fluid temperature [22]. Mathematically, FR is given by the following expression:
S is the solar radiation absorbed by the collector and can be written as:
Collector efficiency factor (F´) is the ratio of the actual useful energy gain (if the absorber surface has the same temperature of local water) to the useful gain [22]. F ´ is a function of many parameters including inlet fluid temperature, outlet fluid temperature, ambient temperature and written as:
Then the heat removal factor was expressed [12], [19], [22] as:
By calculating useful energy, PVT outlet fluid temperature (To) is written as:
The method that is widely used in the literature to calculate PVT electrical performance is to calculate the maximum current power and voltage especially for experimental projects [12], [21]. The method that is proposed here is utilized to calculate electrical performance based on the average temperature of the PV layer. In order to calculate the PV temperature back surface temperature was worked out based on the PVT configuration and the model shown in Figure 2.
Sheet and tube hybrid PVT collector [23]

Table 2 shows the the values of design parameters used in the mathematical model the PVT panel.
The values of design parameters used in the mathematical model
Parameter |
Value |
Parameter |
Value |
---|---|---|---|
A c [m2] |
1.24 |
h |
45 |
Cp [J/kgk] |
4,190 |
h p1 |
0.954 |
Lg [m] |
0.003 |
h p2 |
0.854 |
Lsi [m] |
0.0003 |
a sc |
0.9 |
βc |
0.83 |
βο |
0.0045 |
F′ |
0.956 |
η ο |
0.15 |
FR |
0.948 |
τg |
0.96 |
m′[kg/s] |
0.1 |
U |
150 |
Ub [W/m2k] |
0.84 |
UtT [W/m2k] |
6.81 |
U |
5.81 |
Number of cells (mono crystalline) |
72 |
PV cell temperature (Tcell) [12]:
PV back surface temperature [12]:
Electrical efficiency and output electrical power then worked out by the following expressions:
Output electric power
PV’s cell electric efficiency (ηsc):
In this section, the mathematical model is used to calculate the performance of the PVT. Model validation is discussed and investigation for different inlet temperature is illustrated.
Weather data in Figure 3 were used in the mathematical model to calculate different temperatures that affect PVT performance. This included back surface temperature which is a function of instant solar radiation, ambient temperature and fluid temperature. PV cell temperature was also included which is a function of instant solar radiation, ambient temperature and back surface temperature.
Variation of the solar radiation and ambient temperature throughout the test day [12]

Figure 4 shows ambient temperature, inlet fluid temperature, outlet fluid temperature, PV cell temperature and back surface temperature during Bahaidara experiment day.
Variation of different temperatures that affected the PVT module during the day

The results show that the PVT performance were influenced by several factors that included instant solar radiation, ambient temperature, inlet fluid temperature, PV cell temperature and back surface temperature. As in last figure in next chapter, thermal efficiency was in the range of 72% at 9 AM to 83% at 4 PM and the minimum efficiency was 70.6% between 11 and 12 PM. Thermal efficiency influenced by several factors such as instant solar radiation, ambient temperature, inlet temperature and outlet fluid temperature. Sensitively study is required to investigate the effect of back surface temperature on thermal efficiency. Electrical efficiency was in the range of 14.7% at 9 AM to 15.5% at 4 PM. The minimum efficiency was 14.3% between 11 AM and 12 PM due to the increase in the PV cell temperature. Electrical efficiency decreased by 2.72% due to the increase in PV cell temperature by 19.4% from the morning until 11 PM and increased by 7.6% due to the decrease in PV cell temperature by 48.32% from 12 PM until 4 PM. Figure 5 shows thermal and electrical efficiency during the day.
Thermal and electrical efficiency of the PVT module during the day

The temperature difference between the PV cell temperatures in the mathematical model of the PVT and the experiment was in the range of 0.3 °C to 6.5 °C. However, the trends are in agreement as shown in Figure 6.
Calculated PV cell temperature (Tcell) vs. Bahaidara experimental data [21] (Saudi Arabia-Dhahran)

Back surface temperature was also calculated by the mathematical model throughout the day then validated against the experiment. Figure 7 shows the agreement between back surface temperature (Tbs) for the PVT model and the experiment. Both of experimental and calculated values had the same trend which increased during the day due to the increase in solar radiation and ambient temperature until reaching the maximum temperature at 12 PM before decreasing until the end of the day. The temperature difference between the back surface temperatures in the mathematical model of the PVT and the experiment was in the range of 0.8 °C to 5.5 °C.
Calculated back surface temperature (Tbs) vs. Bahaidara experimental data [21] (Saudi Arabia-Dhahran)

The maximum electrical power during the day was 174 W by the PVT model at 11 PM due to the solar radiation and ambient temperature values while was measured of 210 W at the same time from the experiment. Figure 8 shows the comparison between calculated electrical power by the PVT model and the data from the experiment. Electric power difference between the mathematical model of the PVT and the experiment was in the range of 4 W to 36 W.
Calculated maximum electric power vs. experimental data (Saudi Arabia-Dhahran)

In the previous section, the PVT module is cooled as one area (A = 1.24 m2) and the performance of the PVT at 12 PM were: Ti = 14 °C, Ta = 21 °C, G = 950 W/m2, Qu= 834 J/s, To = 16 °C, thermal efficiency = 70.8%, Tcell = 35.8 °C, electrical efficiency = 14.3% and electrical power = 168 W.
In this section, the PVT is divided into 72 cells (Acell = 0.01722 m2) which represent the total area and the piping was designed to connect cells in series. Configuration of the PVT is shown in Figure 9.
Arrangement of PVT for cells linked thermally in series

Eqs (3, 12, 15) were applied to each cell individually in order to carry out cells temperatures and efficiencies. Based on weather data that are illustrated in Figure 3 and Figure 4, the performances of the PVT module at 12 PM for 14 °C inlet water temperature were determined by considering the 72 cells in series as in Figures 10, 11 and 12. Figure 10 shows individual PV cells temperature for the panel from the inlet at the first cell until cell number 72 where the water leaves the collector. Cell temperatures were increased from inlet to the outlet due to the increase in water temperature.
PVT cell temperature at 12:00 PM and inlet water at 14 °C

PVT electric efficiency at 12:00 PM and inlet water at 14 °C

PVT thermal efficiency at 12:00 PM and inlet water at 14 °C

PVT electrical efficiency was decreased from 14.33% at the inlet cell to 14.22% at the outlet cell due to the increase in the PV cell temperature. Figure 9 shows electrical efficiency for each cell in the panel at 12:00 PM.
PVT thermal efficiency was decreased from 70.79% at the inlet cell to 69.66% at the outlet cell due to the increase in water temperature through the cells. Figure 10 shows thermal efficiency for each cell in the panel at 12:00 PM.
The benefit of connecting cells in series needs to be investigated in the future, this can help to increase the outlet water temperature and to determine the optimum location for
PV cells when the partial PV surface is applied. The outlet water temperature is a key parameter that affects the overall performance of solar cooling systems such as absorption system.
The performance of PVT was calculated based on the heat transfer equations that were discussed in the previous sections. To meet the requirement for solar cooling systems, the best options based on PVT outlet temperature need to be selected and PVT water flow rate need to be optimized in order reach the highest energy saving. The average PV cell temperature should not exceed the maximum operation temperature in the manufacturing specifications of the photovoltaic cells.
The following performance figures are based on 72 panels connected in an array. Each panel has an area of 1.72 m2 and water flowrate of 0.1 kg/s. There are many options for the number of panels that should be linked in series in order to achieve specified outlet temperature. Figure 13 shows the arrangements for a PVT system that could be made of 72 panels. The arrangements could include: one line of 72 panels connected in series (L = 1 and N = 72), 2 lines of 36 panels in series, 3 lines of 24 panels in series, 4 lines of 18 panels in series, 6 lines of 12 panels in series, 8 lines of 9 panels in series, 9 lines of 8 panels in series, 12 lines of 6 panels in series, 18 lines of 4 panels in series, 36 lines of 2 panels in series or 72 panel connected in parallel to the inlet and outlet header (L = 72 and N = 1).
Figure 13. The proposed arrangement for a PVT system, which based on 72 panels connected in an array

Figures 14 to 17 illustrate the performance of PVT module starting from cooling each panel individually (N = 1) then two panels in series (N = 2) until 72 panel in series (N = 72). The number 4 (N = 4) in the x-axis means that the configuration consist of 18 lines (L = 18) in parallel, each lines consist of 4 panels connected in series and the outlet for each lines supply the main header.
PVT outlet fluid temperature for different inlet temperature

For the same numbers of panels, the configuration of connecting them affected the outlet water temperature which was in the range of 25 °C to 110 °C. The more panels connected in series, the higher the outlet temperature is achieved. Figure 14 shows outlet water temperature for different inlet temperature, which have the same trend and the high inlet temperature, the high outlet temperature is reached.
Figure 15 shows average thermal efficiency for different inlet temperature, which was in the range of 15% to 65%. For all cases, the low inlet temperature, the more thermal efficiency was achieved.
PVT thermal efficiency for different inlet temperature

Average electrical efficiency, which was in the range of 8.9% to 13.7%, was also influenced by the configuration of the PVT. The lower inlet temperature, the higher electric efficiency was achieved as in Figure 16.
PVT electrical efficiency for different inlet temperature

Figure 17 shows the average photovoltaic cell temperature, which was in the range of 45 °C to 115 °C for all cases. Cell temperature is an important factor to select the configuration, which should not exceed the manufacturing specification for the maximum temperature.
PVT average cells temperature for different inlet temperature

This research describes the design and analysis of a PVT system for producing electricity and thermal energy. The performance of the PVT system is based on several factors that includes PVT’s materials, design, ambient temperature, inlet and outlet fluid temperature and PV cell temperature. The overall PVT system performance is calculated by using mathematical method.
The results which were based on the climate conditions, show that the PVT performance were influenced by several factors that included instant solar radiation, ambient temperature, inlet fluid temperature, PV cell temperature and back surface temperature. Electrical efficiency was in the range of 14.7% to 15.5% and sensitive to the PV cell temperature. It decreased from 14.72% to 14.27% due to the increase in PV cell temperature from 29.1 °C to 35.8 °C and increased to 15.44% due to the decrease in PV cell temperature to 18.5 °C. Thermal efficiency was in the range of 72% to 83% and was influenced by several factors such as instant solar radiation, ambient temperature, inlet temperature and outlet fluid temperature. Sensitively study is required to investigate the effect of back surface temperature on thermal efficiency.
A PVT arrangement was proposed which connects cells thermally in series in the same panel. Cell temperatures increased from inlet to the outlet due to the increase in water temperature. PVT electrical efficiency decreased from 14.33% at the inlet cell to 14.22% at the outlet cell due to the increase in the PV cell temperature. PVT thermal efficiency decreased from 70.79% at the inlet cell to 69.74% at the outlet cell due to the increase in water temperature through the cells.
Another arrangement was proposed for a PVT system, which based on 72 panels connected in one array. PVT performance curves were worked out for different inlet water temperature. Different configurations of connecting panels in series were also investigated. The more panels connected in series, the higher the outlet temperature. Average thermal efficiency for different inlet temperature was in the range of 15% to 65%. For all cases, the lower the inlet temperature, the more thermal efficiency was achieved. Average electrical efficiency, which was in the range of 8.9% to 13.7%, was also influenced by the configuration of the PVT. The lower the inlet temperature, the higher electric efficiency was achieved. Average photovoltaic cell temperature was in the range of 45 °C to 115 °C for all cases. Cell temperature is an important factor to select the configuration, which should not exceed the manufacturing specification for the maximum temperature.
Further research is required to determine the optimum location for PV cell when the partial PV surface is applied. The outlet water temperature, which is a key parameter that affects the overall performance of solar cooling system, needs to be optimized.
Ac |
collector area |
[m2] |
Cp |
specific heat of the coolant |
[kJ/kgK] |
F |
fin efficiency factor |
[-] |
F′ |
flat plate collector efficiency factor |
[-] |
FR |
heat removal factor |
[-] |
G |
incidence solar irradiance normal to the surface |
[W/m2] |
h |
heat transfer coefficient |
[W/m2] |
hf |
heat transfer coefficient to fluid |
[W/m2] |
ho |
heat transfer coefficient to ambient |
[W/m2] |
hp1 |
penalty factor due to the glass cover of PV module |
[-] |
hp2 |
penalty factor due to the absorber below PV module |
[-] |
hT |
heat transfer coefficient back surface of tedlar to fluid |
[W/m2K] |
I(t) |
incident solar intensity |
[W/m2] |
Impp |
electric current at maximum power point |
[A] |
Ip |
solar radiation perpendicular to collector surface |
[W/m2] |
Is |
solar radiation reaching the solar collector |
[W/m2] |
Lg |
the thickness of glass cover |
[m] |
Lsi |
the thickness of silicon solar cell |
[m] |
m′ |
mass flowrate of the coolant |
[kg/s] |
Q |
heat transfer rate |
[kW] |
Qu |
useful energy output from the solar collector |
[kW] |
Ta |
ambient temperature |
[°C] |
Tf |
fluid temperature |
[°C] |
Tin |
inlet temperature of the coolant |
[°C] |
Tout |
outlet temperature of the coolant |
[°C] |
Tpm |
mean temperature for the absorber plate collector |
[°C] |
Ub |
an overall back loss coefficient from flowing water to ambient |
[W/m2K] |
UL |
an overall heat loss coefficient from the PV/T water collector to the environment |
[W/m2K] |
Ut |
an overall heat transfer coefficient from solar cell to ambient through glass cover |
[W/m2K] |
UT |
an overall heat transfer coefficient from solar cell to flowing water through tedlar |
[W/m2K] |
Utf |
an overall heat transfer coefficient from glass to water through solar cell and tedlar |
[W/m2K] |
UtT |
an overall heat transfer coefficient from glass to tedlar through solar cell |
[W/m2K] |
Vmpp |
electric voltage at maximum power point |
[V] |
α |
absorbance |
βc |
packing factor of solar cell |
βo |
photovoltaic temperature coefficient |
η |
efficiency |
η elc |
photovoltaic electrical efficiency |
η o |
reference cell efficiency |
η th |
photovoltaic thermal efficiency |
η tot |
photovoltaic overall efficiency |
τ |
transmittance |
ϵ |
emittance |
Coefficient of Performance
Photovoltaic Panel
Solar Fraction
Towards a Methanol Economy based on Homogeneous Catalysis: Methanol to H2 and CO2 to Methanol ,Chemical Communications , Vol. Vol. 51 (No. 31), :6714-67252015, https://doi.org/10.1039/C4CC09471A
, A proposed Coal-to-methanol Process with CO2 capture combined Organic Rankine Cycle (ORC) for Waste Heat recovery ,Journal of Cleaner Production , Vol. Vol. 129 , :53-642016, https://doi.org/10.1016/j.jclepro.2016.04.123
, DFT Study of Formaldehyde and Methanol Synthesis from CO and H2 on Ni (111) ,The Journal of Physical Chemistry B , Vol. Vol. 108 (No. 38), :14535-145402004, https://doi.org/10.1021/jp0493374
, Towards full One-pass conversion of Carbon Dioxide to Methanol and Methanol-derived Products ,Journal of Catalysis , Vol. Vol. 309 , :66-702014, https://doi.org/10.1016/j.jcat.2013.09.005
, Synthesis of Acetic Acid from Methanol alone by Homogeneous Metal Complex Catalyst, Part II ,Journal of Molecular Catalysis A: Chemical , Vol. Vol. 97 (No. 1), :35-401995, https://doi.org/10.1016/1381-1169(94)00073-5
, Thermochemical Biorefinery based on Dimethyl Ether as Intermediate: Technoeconomic assessment ,Applied Energy , Vol. Vol. 102 , :950-9612013, https://doi.org/10.1016/j.apenergy.2012.09.051
, The Potential of Methanol as a Fuel for Flex-fuel and dedicated Spark-ignition Engines ,Applied Energy , Vol. Vol. 102 , :140-1492013, https://doi.org/10.1016/j.apenergy.2012.05.065
, Fuel from the Synthesis Gas – the Role of Process Engineering ,Applied Energy , Vol. Vol. 74 (No. 1-2), :85-932003, https://doi.org/10.1016/S0306-2619(02)00134-4
, Methanol Synthesis: A Short Review of Technology Improvements ,Catalysis Today , Vol. Vol. 64 (No. 1-2), :3-82001, https://doi.org/10.1016/S0920-5861(00)00503-4
, Dynamic modeling of the Methanol Synthesis Fixed-bed Reactor ,Computers & Chemical Engineering , Vol. Vol. 48 , :325-3342013, https://doi.org/10.1016/j.compchemeng.2012.09.013
, Methanol Synthesis from CO2 Hydrogenation over Copper based Catalysts ,Reaction Kinetics, Mechanisms and Catalysis , Vol. Vol. 110 (No. 1), :131-1452013, https://doi.org/10.1007/s11144-013-0587-9
, Comparative Energetic assessment of Methanol production from CO2: Chemical versus Electrochemical Process ,Applied Energy , Vol. Vol. 165 , :1-132016, https://doi.org/10.1016/j.apenergy.2015.12.027
, Efficient Methanol Synthesis: Perspectives, Technologies and Optimization Strategies ,Progress in Energy and Combustion Science , Vol. Vol. 56 , :71-1052016, https://doi.org/10.1016/j.pecs.2016.06.001
, Numerical Investigation on Performance of Coal Gasification under Various Injection Patterns in an entrained Flow Gasifier ,Applied Energy , Vol. Vol. 100 , :218-2282012, https://doi.org/10.1016/j.apenergy.2012.05.013
, Syngas yield during Pyrolysis and Steam Gasification of Paper ,Applied Energy , Vol. Vol. 86 (No. 9), :1813-18212009, https://doi.org/10.1016/j.apenergy.2009.01.025
, Considerations on the Steady-state modeling of Methanol Synthesis Fixed-bed Reactor ,Chemical Engineering Science , Vol. Vol. 66 (No. 2), :152-1622011, https://doi.org/10.1016/j.ces.2010.09.036
, Analysis of a feasible Polygeneration System for Power and Methanol Production taking Natural Gas and Biomass as Materials ,Applied Energy , Vol. Vol. 87 (No. 9), :2846-28532010, https://doi.org/10.1016/j.apenergy.2009.07.001
, Hydrogen from Biogas: Catalytic Tri-reforming Process with Ni/La Ce O mixed Oxides ,Applied Catalysis B: Environmental , Vol. Vol. 148 , :91-1052014, https://doi.org/10.1016/j.apcatb.2013.10.043
, Syngas Production by Methane Oxy-steam reforming on Me/CeO2 (Me = Rh, Pt, Ni) Catalyst lined on Cordierite Monoliths ,Applied Catalysis B: Environmental , Vol. Vol. 162 , :551-5632015, https://doi.org/10.1016/j.apcatb.2014.07.028
, Energy Resources and use: The Present Situation and Possible Paths to the Future ,Energy , Vol. Vol. 33 , :842-8572008, https://doi.org/10.1016/j.energy.2007.09.009
, Conceptual design of Coke-oven Gas assisted Coal to Olefins Process for high Energy efficiency and low CO2 emission ,Applied Energy , Vol. Vol. 133 , :197-2052014, https://doi.org/10.1016/j.apenergy.2014.07.105
, Technological approaches and Policy analysis of integrated Water Pollution prevention and Control for the Coal-to-methanol Industry based on best available Technology ,Journal of Cleaner Production , Vol. Vol. 113 , :231-2402016, https://doi.org/10.1016/j.jclepro.2015.11.077
, Co-gasification of Biomass and Coal for Methanol Synthesis ,Applied Energy , Vol. Vol. 74 (No. 3-4), :393-4032003, https://doi.org/10.1016/S0306-2619(02)00184-8
, Evolution of Syngas from Cardboard Gasification ,Applied Energy , Vol. Vol. 86 (No. 9), :1732-17402009, https://doi.org/10.1016/j.apenergy.2008.11.018
, Carbon Footprint evaluation of Coal-to-methanol Chain with the Hierarchical Attribution management and Life Cycle assessment ,Energy Conversion and Management , Vol. Vol. 124 , :168-1792016, https://doi.org/10.1016/j.enconman.2016.07.005
, What’s the most Cost-effective Policy of CO2 targeted Reduction: An Application of aggregated Economic Technological Model with CCS? ,Applied Energy , Vol. Vol 112 , :866-8752013, https://doi.org/10.1016/j.apenergy.2013.01.047
, Energy related CO2 emissions and the progress on CCS Projects: A Review ,Renewable and Sustainable Energy Reviews , Vol. Vol. 31 , :368-3852014, https://doi.org/10.1016/j.rser.2013.12.002
, A predictive Kinetic Model of Sulfur release from Coal ,Fuel , Vol. Vol. 91 (No. 1), :213-2232012, https://doi.org/10.1016/j.fuel.2011.08.017
, Effect of reaction Parameters on the Quality of captured Sulfur in Claus Process ,Applied Energy , Vol. Vol. 104 , :772-7762013, https://doi.org/10.1016/j.apenergy.2012.12.015
, Acid Gas to Syngas (AG2S™) Technology applied to Solid Fuel Gasification: Cutting H2S and CO2 emissions by improving Syngas Production ,Applied Energy , Vol. Vol. 184 , :1284-12912016, https://doi.org/10.1016/j.apenergy.2016.06.040
, Process for reducing CO2 and producing Syngas ,Priority Patent: PCT Application Number WO, 15457, A1 , 2015
, Experimental examination of Syngas recovery from Acid Gases ,Applied Energy , Vol. Vol. 164 , :64-682016, https://doi.org/10.1016/j.apenergy.2015.11.025
, Characterization of Several kinds of Coal and Biomass for Pyrolysis and Gasification ,Fuel , Vol. Vol. 152 , :138-1452015, https://doi.org/10.1016/j.fuel.2014.09.054
, Software Tools overview: Process integration, modelling and optimisation for Energy saving and pollution reduction ,Asia-Pacific Journal of Chemical Engineering , Vol. Vol. 6 , :696-7122011, https://doi.org/10.1002/apj.469
, PRSV: An improved Peng – Robinson Equation of State for pure Compounds and Mixtures ,The Canadian Journal of Chemical Engineering , Vol. Vol. 64 , :323-3331986, https://doi.org/10.1002/cjce.5450640224
, PRSV – An improved Peng-Robinson Equation of State with new mixing Rules for Strongly Nonideal Mixtures ,The Canadian Journal of Chemical Engineering , Vol. Vol. 64 , :334-3401986, https://doi.org/10.1002/cjce.5450640225
, GASDS: A Kinetic-based Package for Biomass and Coal Gasification ,Chemical Engineering , Vol. Vol. 50 , 2016
, A Predictive Multi-step Kinetic Model of Coal devolatilization ,Fuel , Vol. Vol. 89 (No. 2), :318-3282010, https://doi.org/10.1016/j.fuel.2009.07.023
, Multi-scale Kinetic modeling and Experimental investigation of Syngas production from Coal Gasification in Updraft Gasifiers ,Energy & Fuels , Vol. Vol. 29 (No. 6), :3972-39842015, https://doi.org/10.1021/acs.energyfuels.5b00648
, Chapter One-Pyrolysis, Gasification, and Combustion of Solid Fuels ,Advances in Chemical Engineering , Vol. Vol. 49 , :1-942016, https://doi.org/10.1016/bs.ache.2016.09.001
, Natural Gas sweetening Process Simulation and Optimization: A Case Study of Khurmala Field in Iraqi Kurdistan Region ,Journal of Natural Gas Science and Engineering , Vol. Vol. 14 , :116-1202013, https://doi.org/10.1016/j.jngse.2013.06.005
, Model-based optimization of Sulfur Recovery Units ,Computers & Chemical Engineering , Vol. Vol. 66 , :244-2512014, https://doi.org/10.1016/j.compchemeng.2014.01.019
, Modeling of the Kinetics for Methanol Synthesis using Cu/ZnO/Al2O3/ZrO2 Catalyst: Influence of Carbon Dioxide during Hydrogenation ,Industrial & Engineering Chemistry Research , Vol. Vol. 48 , :10448-104552009, https://doi.org/10.1021/ie901081f
, Advances in Sulfur Chemistry for treatment of Acid Gases ,Progress in Energy and Combustion Science , Vol. Vol. 54 , :65-922016, https://doi.org/10.1016/j.pecs.2015.11.001
, Multi-scale modeling of Claus Thermal Furnace and Waste Heat Boiler using detailed Kinetics ,Computers & Chemical Engineering , Vol. Vol. 59 , :219-2252013, https://doi.org/10.1016/j.compchemeng.2013.05.028
, Hierarchical and Comparative Kinetic modeling of Laminar Flame Speeds of Hydrocarbon and oxygenated Fuels ,Progress in Energy and Combustion Science , Vol. Vol. 38 (No. 4), :468-5012012, https://doi.org/10.1016/j.pecs.2012.03.004
, Revised Kinetic Scheme for Thermal Furnace of Sulfur Recovery Units ,Chemical Engineering Transactions , Vol. Vol. 32 , :1185-12902013
, Kinetic modeling of the Interactions between NO and Hydrocarbons at high Temperature ,Combustion and Flame , Vol. Vol. 135 (No. 1-2), :97-1122003, https://doi.org/10.1016/S0010-2180(03)00152-4
, The low-temperature hydrolysis of Carbonyl Sulfide and Carbon Disulfide: A Review ,Catalysis Today , Vol. Vol. 59 (No. 3-4), :443-4642000, https://doi.org/10.1016/S0920-5861(00)00309-6
, A Review of the Water Gas Shift Reaction Kinetics ,International Journal of Chemical Reactor Engineering , Vol. Vol. 8 (No. 1), 2010, https://doi.org/10.2202/1542-6580.2238
, Modeling and Simulation of Hydrogen Generation from high-temperature and low-temperature Water Gas Shift Reactions ,International Journal of Hydrogen Energy , Vol. Vol. 33 (No. 22), :6644-66562008, https://doi.org/10.1016/j.ijhydene.2008.08.039
, Experimental and Simulation of both Pd and Pd/Ag for a Water Gas Shift Membrane Reactor ,Separation and Purification Technology , Vol. Vol. 25 (No. 1-3), :549-5712001, https://doi.org/10.1016/S1383-5866(01)00168-X
, Economic analysis of a combined Energy-methanol Production Plant ,Applied Energy , Vol. Vol. 88 (No. 12), :4891-48972011, https://doi.org/10.1016/j.apenergy.2011.06.028
, Unified modeling and feasibility Study of Novel Green Pathway of Biomass to Methanol/dimethylether ,Applied Energy , Vol. Vol. 145 , :278-2942015, https://doi.org/10.1016/j.apenergy.2015.02.019
, A Review of Cleaner production Methods for the Manufacture of Methanol ,Journal of Cleaner Production , Vol. Vol. 57 , :19-372013, https://doi.org/10.1016/j.jclepro.2013.06.017
, The Sotacarbo Coal gasification Experimental Plant for a CO2-free Hydrogen Production ,International Journal of Hydrogen Energy , Vol. Vol. 35 (No. 18), :9836-98442010, https://doi.org/10.1016/j.ijhydene.2009.10.024
, A Kinetic approach to the Mathematical Model of Fixed bed Gasifiers ,Computers & Chemical Engineering, , Vol. Vol. 35 (No. 5), :928-9352011, https://doi.org/10.1016/j.compchemeng.2011.01.036
, Comparison of Shell, Texaco, BGL and KRW Gasifiers as Part of IGCC Plant Computer Simulations ,Energy Conversion and Management , Vol. Vol. 46 (No. 11-12), :1767-17792005, https://doi.org/10.1016/j.enconman.2004.09.004
, Sulfur Recovery Units: Adaptive Simulation and Model Validation on an Industrial Plant ,Industrial & Engineering Chemistry Research , Vol. Vol. 49 (No. 12), :5714-57242010, https://doi.org/10.1021/ie901749t
, Design of SRU Thermal Reactor and Waste Heat Boiler considering Recombination Reactions ,Procedia Engineering , Vol. Vol. 42 , :376-3832012, https://doi.org/10.1016/j.proeng.2012.07.429
, Economic assessment of Temperature swing adsorption Systems as Claus Tail Gas Clean up units ,Chemical Engineering Science , Vol. Vol. 126 , :186-1952015, https://doi.org/10.1016/j.ces.2014.12.015
,